dc.description.abstract | The present study aims to evaluate the feasibility of using condensed water,
collected by means of air conditioning devices, for non-potable purposes in the aeronautics barracks, specifically in the 3rd Integrated Center for Air Defense and Air
Traffic Control (CINDACTA III) , in Recife-PE. For this purpose, the air conditioners
were quantified according to their cooling power (BTU), the flow of condensed water
generated by the equipment was determined, the destination of the water used was
established and, finally, an analysis of the feasibility of implementing the system was
carried out. reuse. From the results found, it was found that CINDACTA III has, in its
administrative building, 39 air conditioners, of which they were listed for study 12, in
which a monthly production of 4.70 m³ of condensed water was determined,
equivalent to 34.50 % of demand from the irrigation activity of landscaped areas on
the site. In addition to savings in potable water consumption, the implementation of
the system allows for a payback period of just over three years as a payback period.
Thus, in addition to favoring the economy of the establishment, the measure also
contributes to the rational use and conservation of water, since drinking water will no
longer be used for non-noble purposes. | pt_BR |
dc.relation | ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS - ABNT. Sistemas prediais
de água fria e água quente - Projeto, execução, operação e manutenção, ABNT
NBR 5626:2020. Rio de Janeiro, 2020. 56 p.
BRASIL. PORTARIA Nº 518, DE 25 DE MARÇO DE 2004. Dispõe sobre os
procedimentos e responsabilidades relativos ao controle e vigilância da
qualidade da água para consumo humano e seu padrão de potabilidade. Diário
Oficial da União, Brasília, 26 mar. 2004.
CALDAS, J.; CAMBOIM, W. L. L. Aproveitamento da água dos aparelhos
condicionadores de ar para fins não potáveis: avaliação da viabilidade de
implantação em um bloco do Unipê. Interscientia, v. 5, n. 1, p. 166-188, 2017.
CARVALHO, C. O. C.; GOUVEIA, D. M.; ACCARDO, E. Reaproveitamento da água
condensada de aparelhos de ar-condicionado para uso em laboratórios de
química. Re-Vista, v. 3, n. 5, p. 46-59, 2018.
CUNHA, K. T.; KLUSENER FILHO, L. C.; SCHRODER, N. T. Reaproveitamento da
água de condensação de equipamentos de ar condicionado. Revista de Iniciação
Científica da ULBRA, n. 14, p. 166-176, 2016.
DAMASIO, A. C.; SILVA, J. S.; VASCONCELOS, E. C. Utilização da água dos
condicionadores de ar para manutenção das áreas verdes do Instituto Federal de
Pernambuco - campus Recife. Revista Caravana - Diálogos entre Extensão e
Sociedade, v. 6, n. 1, p. 179-197, 2021.
EDUARDO. Qual melhor marca de caixa d’água de polietileno?. Clube de
Veículos Militares Antigos do Rio de Janeiro, Rio de Janeiro, 15 de abr. de 2019.
Disponível em: <https://cvmarj.com.br/blog/qual-melhor-marca-de-caixa-d-agua-depolietileno/>. Acesso em: 29 de set. de 2021.
FORTES, P. D.; JARDIM, PATRICK W. C. F. P. M. G.; FERNANDES, J. G.
Aproveitamento de água proveniente de aparelhos de ar condicionado. In: Simpósio
de Excelência em Gestão e Tecnologia, 12., 2015, Resende. Anais [...]. Resende:
AEDB, 2015. p. 1-16.
MOTA, T. R.; OLIVEIRA, D. M.; INADA, P. Reutilização da água dos aparelhos de ar
condicionado em uma escola de ensino médio no município de Umuarama-PR.
In: Encontro Internacional de Produção Científica CESUMAR, 7., 2011, Maringá.
Anais [...]. Maringá: CESUMAR, 2011. p. 1-5.
MOURA, P. G.; ARANHA, F. N.; HANDAM, N. B.; MARTIN, L. E.; SALLES, M. J.;
CARVAJAL, E.; JARDIM, R. SOTERO-MARTINS, A. Água de reúso: uma alternativa
sustentável para o Brasil. Engenharia Sanitária Ambiental, v. 25, n. 6, p. 791-808,
2020.
PRADO, A. R. M.; SOARES, A. E. P.; SILVA, S. R. Análise técnico-econômica da
utilização de água de condensação para fins não potáveis em um campus
universitário. Revista Nacional de Gerenciamento de Cidades, v. 8, n. 65, p. 158-
172, 2020.
RECIFE. Lei nº 16.292/97, de 29 de janeiro de 1997 (Regulamentada pelo Decreto
nº 26.688/2012) – Regula as atividades de edificações e instalações, no
município do Recife, e dá outras providências. Recife, 1997.
REZENDE, A. T. Reúso urbano de água para fins não potáveis no Brasil. 2016.
106 f. Trabalho de Conclusão de Curso (Bacharelado em Engenharia Ambiental e
Sanitária) – Universidade Federal de Juiz de Fora, Juiz de Fora, 2016.
RODRIGUES, J. O. N.; SILVA, T. C.; ATHAYDE JÚNIOR, G. B. Análise qualiquantitativa da água condensada gerada por aparelhos de ar-condicionado. Revista
Eletrônica de Gestão e Tecnologias Ambientais (GESTA), v. 7, n. 2, p. 160-174,
2019.
ROCHA, D. P. B. Sistema de reuso de água proveniente de aparelhos de ar
condicionados para fins não potáveis: estudo de caso aplicado ao Centro de
Tecnologia da UFRN. 2017. 19 f. Trabalho de Conclusão de Curso (Bacharelado em
Engenharia Civil) – Universidade Federal do Rio Grande do Norte, Natal, 2017.
SILVA, J. K.; NUNES, L. G. C. F.; SILVA, S. R. Conservação de águas nas
cidades. In: SILVA, Simone Rosa. Conservação de água em prédios públicos no
município do Recife. Recife: Edupe, 2018. p. 29-46.
SOARES, M. C. D. M. Reuso de água dos aparelhos de ar condicionado para
fins não potáveis em prédio público administrativo. 2017. 69 f. Trabalho de
Conclusão de Curso (Bacharelado em Engenharia Civil) – Universidade de
Pernambuco, Recife, 2017.
SOARES, A. E. P.; PRADO, A. R. M.; SILVA, S. R. Aproveitamento da água de
condensação de aparelhos condicionadores de ar em campus universitário.
In: Simpósio de Recursos Hídricos do Nordeste, 15., 2020, Caruaru. Anais [...].
Caruaru: ABRHidro, 2020. 1-9.
VASCONCELOS, E. C. Uso de águas pluviais e residuais em instalações
prediais: Subsídios para gestão ambiental em prédios públicos. 2016. 117 f.
Dissertação (Mestrado em Gestão Ambiental) – Instituto Federal de Pernambuco,
Recife, 2016. | pt_BR |
dc.description.resumo | O presente estudo tem como objetivo avaliar a viabilidade do aproveitamento da
água condensada, coletada por meio de aparelhos condicionadores de ar, para fins
não potáveis no quartel da aeronáutica, especificamente no 3º Centro Integrado de
Defesa Aérea e Controle de Tráfego Aéreo (CINDACTA III), em Recife-PE. Para
isso, foram quantificados os aparelhos de ar condicionado conforme sua potência de
refrigeração (BTU), determinada a vazão de água condensada gerada pelos
equipamentos, estabelecida a destinação da água aproveitada e, por fim, realizada a
análise da viabilidade da implementação do sistema de reaproveitamento. A partir
dos resultados encontrados, verificou-se que o CINDACTA III detém, em seu prédio
administrativo, 39 aparelhos condicionadores de ar, dos quais foram elencados para
o estudo 12, em que foi determinada uma produção de 4,70 m³ mensais de água
condensada, equivalendo a 34,50% da demanda da atividade irrigação de áreas
ajardinadas do local. Além da economia no consumo de água potável, a implantação
do sistema possibilita um pay back de pouco mais de três anos como período de
retorno do investimento. Assim, além de favorecer a economia do estabelecimento,
a medida também contribui para o uso racional e conservação da água, uma vez
que deixará de ser utilizada a água potável para fins não nobres. | pt_BR |